Ring earthing
Ring earthing is part of a lightning protection system. Its main purpose is to carry lightning current into the ground, supporting the safe operation of electrical systems and protecting people and animals from electric shock.
A ring earth electrode is installed outside the building as a closed loop.
PN-EN 62305-3, which addresses the design of lightning protection earthing, distinguishes the following arrangements:
- Type A: horizontal and vertical electrodes outside the structure, each connected to a down conductor
- Type B: a foundation, ring or mesh earth-electrode arrangement
Common materials include copper-bonded steel, hot-dip galvanised steel, uncoated steel and pure copper. Copper offers high current-carrying capacity and a service life of around 30 years. Corrosion-resistant and copper materials help resist deterioration in the ground.
A ring electrode made from hot-dip galvanised steel tape is buried at a depth of at least half a metre. It is generally laid about one metre from the foundations in a separate trench, providing adequate contact with the soil while avoiding disturbance to the building's stability.
Soil moisture should be considered when excavating. For buildings with large roof areas, mesh electrodes should extend beyond the area sheltered by the roof.
A correctly designed and installed earthing system helps carry lightning energy safely into the ground. A faulty system can leave energy undissipated, resulting in fire, electric shock or damage to connected household equipment.